APPLICATION ENGINEERING

Pump & empty-pipe monitoring

Use local liquid presence as one input to a defined pump protection strategy.

MEDIA TO REVIEW

Compatible process liquids in transfer lines, balance tanks and pump feed systems

What the sensor needs to do

Liquid covering a sensor is not proof of flow, adequate suction pressure or acceptable pump operating conditions.

LocationControl objectiveSelection focus
Pump inlet pipingA local dry/wet process input.Position the tip where drainage is representative.
Low tank levelA permissive related to available liquid.Allow enough time and volume before suction becomes unacceptable.
Intermittent transferA defined empty-pipe indication.Account for air slugs, startup filling and trapped liquid.

Installation and integration

Review the location with the process designer and pump supplier. Avoid a low pocket that stays flooded after the usable suction path empties. Include the sensor response, PLC cycle, configured delays and actuator stopping behavior in the timing assessment.

A representative test plan

Observe the real sequence during controlled drain-down and refill. Compare the local sensor state with independent evidence of the process condition. Test the complete control chain through the PLC to the final response; checking the LED alone leaves most of the chain unverified.

A common selection mistake

Advertising a single standard point switch as a complete certified dry-run or overfill safety system. The protection function depends on the full design and its required integrity.

What to include in your inquiry

  • Pump duty, flow and minimum acceptable suction condition
  • Tank/pipe layout with proposed sensor position
  • Start, stop and restart logic
  • Response time, delays and required protection standard

Choose a starting point

Review Lisen electronic point switches for a configured industrial package or Baumer CleverLevel families for a documented manufacturer selection. Selection depends on the exact medium, configuration and duty. A family name alone is insufficient to approve the application.

Technical references

Lisen technical reference — English summary of the supplied 2024-11-25 manual ↗

Baumer — CleverLevel point level sensor portfolio (reviewed 2026-10-03) ↗

Family information and engineering guidance are a starting point. Confirm the exact order-code documentation and installation requirements.