Identify the source of chattering
A changing signal may come from a turbulent surface, bubbles, a poorly placed sensor, unstable power or marginal media response. Filtering should follow diagnosis. A mechanical retention pocket or wiring problem is unlikely to be solved reliably by simply increasing delay.
Calculate the whole response path
Include sensor response, configured damping, PLC scan or timer behavior and actuator reaction. Some applications tolerate a delayed stable indication; others need prompt detection of an empty pipe or rising level.
A delay set independently in both the sensor and PLC can accumulate unnoticed. Keep the values in the commissioning record and review the worst-case sequence.
Use acceptance criteria
Test short disturbances that should be ignored and sustained changes that must be acted on. Verify both covered-to-uncovered and uncovered-to-covered transitions, since the desired behavior may differ. A setting is acceptable only when it rejects nuisance events while meeting the required process response.
What to confirm for your application
- Cause and duration of nuisance events
- Maximum permitted detection delay
- Sensor and PLC timer settings
- Both transition directions
- Documented functional test