20 mA switching load is not a 4–20 mA level signal

A maximum switching current of 20 mA describes the load an output can drive. It does not mean the sensor provides a 4–20 mA continuous level measurement.

3 10 月 2026 · 2 minute read

Read the output specification carefully

The supplied Lisen and legacy LBFS references list transistor switching outputs and a maximum load current. The output changes between defined states. A 4–20 mA transmitter instead encodes a continuously varying measured value in the loop current. These are different interface types.

Separate supply consumption from load capability

A datasheet may list sensor supply consumption as well as the maximum output load. Those numbers answer different questions. Do not add a high-current relay coil or solenoid merely because the power supply can deliver enough current. The sensor output must be rated for the connected load.

If an interface module is needed, its input, protection and failure behavior become part of the design. Specify it with the sensor package rather than leaving it to an improvised field modification.

Confirm the receiving device

Ask for the PLC or controller input specification. An analog input expecting a current-loop signal will not automatically interpret a transistor switch as a level value. Use an appropriately designed interface and keep the process requirement clear: a point switch still supplies only a threshold state.

What to confirm for your application

  • Switching versus analog input requirement
  • Sensor output load limit
  • Supply consumption and voltage tolerance
  • Interface requirements
  • Actual wet/dry truth table

References

Baumer CleverLevel LBFS datasheet — supplied reference, EN/2018-03-01

Lisen technical reference — English summary of the supplied 2024-11-25 manual

Technical guidance. Verify the current order-code documentation and your plant requirements before applying a recommendation.