Skip to content
LISEN BAUMER · Point Level Sensor
◎ EN
Request a quote

Testing & maintenance

How to design a useful level switch sample test

A good sample test turns a Point Level Sensor advantage into evidence: a repeatable covered state, a useful empty state and an acceptable response after draining.

4 10 月 2026 · 3 minute read

POINT LEVEL SENSOR / PRACTICAL ADVANTAGE

Make the advertised benefit measurable

A good sample test turns a Point Level Sensor advantage into evidence: a repeatable covered state, a useful empty state and an acceptable response after draining. Define those results before testing. The comparison becomes more valuable when all candidate sensors see the same medium, geometry and conditions.

Agree on pass criteria first

List which states must produce covered and uncovered outputs. Include product, empty condition, foam, residue and cleaning fluid where relevant. Define the permitted time to switch and reset. Without those criteria, a video showing an LED change can be interpreted too generously.

Use representative conditions

Test actual product or a documented representative sample. Record temperature, concentration and mounting arrangement. Repeat immersion and draining without wiping the tip between every cycle if the real process leaves residue.

For mixtures, powders or temperature-sensitive products, include the relevant extremes. State clearly what the bench test does not reproduce, such as full vessel pressure or long-term abrasive exposure.

Keep a transferable record

Record the complete sensor code, settings, wiring and observations. A pass applies to those documented conditions. Use the result to support selection, then verify the installed control function during commissioning. A supplier demonstration should not be presented as a guarantee for every formulation or operating condition.

What to confirm for your application

  • Written wet/dry and intermediate-state criteria
  • Representative sample and temperature
  • Repeated transitions and residue
  • Complete sensor configuration
  • Limits of the test and site acceptance plan

Make the result reproducible

Agree the test criteria before seeing the results. For a residue problem, specify the draining and waiting sequence rather than dipping the sensor repeatedly until an acceptable response appears. Include repeated cycles and the relevant range of product conditions. Record a failure with the same care as a success; it may show that the location, configuration or sensing principle needs to change. Keep the original measurements and the final approved settings together. Any required certified safety or hygienic acceptance follows its own applicable procedure.

Review item Meaning Action
Identity Full order code, serial number and parameter set Allows the tested configuration to be ordered again.
Conditions Medium, temperature, mounting and sequence Allows the difficult conditions to be repeated.
Observations Indicator, electrical output, PLC state and timing Separates sensing behavior from integration problems.
Decision Accepted range, limitations and open actions Prevents one successful observation from becoming a universal claim.

Explore the Point Level Sensor advantages guide or compare the available sensor families for this duty.

Put this Point Level Sensor advantage to work

Compare the Lisen and Baumer Point Level Sensor families, prepare an application brief, or use the sensor selector to organize the next technical discussion.

References

Baumer CleverLevel LBFS datasheet — supplied reference, EN/2018-03-01

Lisen technical reference — English summary of the supplied 2024-11-25 manual

Technical guidance. Verify the current order-code documentation and your plant requirements before applying a recommendation.

Continue reading

LISEN · BAUMER

Put Point Level Sensor advantages to work in your process.

Tell us the medium, switching task, temperature, pressure and connection. We will help define the sensor family and installation package.

Request a quote
Contact on WhatsApp
滚动至顶部