Skip to content
LISEN BAUMER · Point Level Sensor
◎ EN
Request a quote

Media behavior

Level switches for sticky products and coating

For sticky products, the valuable benefit is a sensor that can distinguish a drained coating from true product coverage.

4 10 月 2026 · 3 minute read

POINT LEVEL SENSOR / PRACTICAL ADVANTAGE

Recover a useful empty signal after draining

For sticky products, the valuable benefit is a sensor that can distinguish a drained coating from true product coverage. Selected configurable or adaptive point sensors can help achieve that behavior. Validate with aged residue and realistic drain times so the chosen setting supports production rather than merely a clean-water demonstration.

Separate coverage from residue

A switch should recognize the required presence state and return correctly after the product leaves. Thick film, strings of product, crystals or a deposit bridge can make the empty state resemble immersion. A short tip can reduce product retention but cannot guarantee immunity to every deposit.

Installation can create the problem

A long socket, pocket or poorly draining adapter may retain product around an otherwise suitable sensor. Review the cross-section of the whole connection. The sensor should reach the intended process region rather than monitor liquid trapped in a recess.

Changing thresholds alone can mask a mechanical problem. Before adjusting sensitivity, inspect whether material is genuinely remaining at the sensing position.

Test after aging

Run repeated production and cleaning cycles, then include a realistic idle period. Some products become more troublesome as they cool, dry or cure. Record both false-covered events and failures to detect new product. If cleaning is needed at a defined interval, include that requirement in the maintenance plan and cost comparison.

What to confirm for your application

  • Residue thickness and drainage time
  • Nozzle and adapter geometry
  • Product changes during cooling or drying
  • Available threshold adjustment
  • Maintenance access and cleaning method

Test the drained condition deliberately

The amount and structure of residue depend on temperature, waiting time, shear and installation geometry. Reproduce the actual drain-down rather than wiping the tip between every observation. If settings are changed to reject a deposit, repeat the least favorable covered condition to ensure the adjustment did not remove the ability to detect usable product. A mounting pocket may dominate the result; in that case, relocating or changing the adapter can be more effective than further sensitivity adjustment.

Review item Meaning Action
Fully covered Bulk product at the sensing tip Confirm reliable material-present detection.
Recently drained Thick wet film or product bridge remains Observe whether the required empty state is reached.
After cleaning Residue and temperature change Check recovery and repeatability over the cycle.

Explore the Point Level Sensor advantages guide or compare the available sensor families for this duty.

Put this Point Level Sensor advantage to work

Compare the Lisen and Baumer Point Level Sensor families, prepare an application brief, or use the sensor selector to organize the next technical discussion.

References

Baumer CleverLevel LBFS datasheet — supplied reference, EN/2018-03-01

Lisen technical reference — English summary of the supplied 2024-11-25 manual

Technical guidance. Verify the current order-code documentation and your plant requirements before applying a recommendation.

Continue reading

LISEN · BAUMER

Put Point Level Sensor advantages to work in your process.

Tell us the medium, switching task, temperature, pressure and connection. We will help define the sensor family and installation package.

Request a quote
Contact on WhatsApp
滚动至顶部