Two different questions
A high-level switch answers whether material has reached a chosen location. A continuous transmitter answers how high the surface is now. A discrete PLC input cannot turn a single switch into a continuous inventory instrument. Installing switches at several heights gives several thresholds, not a continuous measurement.
For a vessel that needs both inventory and an independent high-level signal, the useful design may contain both kinds of device. Decide which function is required before comparing prices.
When a compact point switch makes sense
Consider an electronic point switch for a low-level permissive, an empty-pipe indication or a product-present signal. Confirm that material actually reaches the sensing tip at the required condition. A wetted tip at a low nozzle does not prove that the entire vessel contains usable product.
A practical example
A batch tank needs a percentage display for operators and a low-level signal for a transfer pump. The continuous sensor provides the display. A separately placed point switch can support the low-level function. The engineer still defines alarm logic, delays, failure response and the required independence; two devices alone do not establish a safety function.
What to confirm for your application
- Required output: switching or continuous value
- Location of each alarm and available mounting points
- Expected response to power loss and a broken cable
- Whether inventory, volume or only material presence is needed
References
Baumer CleverLevel LBFS datasheet — supplied reference, EN/2018-03-01
Lisen technical reference — English summary of the supplied 2024-11-25 manual
Endress+Hauser — Basics of continuous level measurement
Technical guidance. Verify the current order-code documentation and your plant requirements before applying a recommendation.